TYPE CEA, ACEA AND ZHLA COMBUSTION & FLAMMABILITY PROPERTIES
*Combustion & Flammability Properties:
Test
Value
Vertical Burn (Material)
UL94
V-0 Rating No Flaming Drips
Vertical Burn (Conduit)
UL360
Pass No Flaming Drips
Oxygen Index %
D2863
28.5
Flame Spread Index
ASTM E162
4.0 No Flaming Drips
Flame Propagation
ASTM C542 (NFPA-130)
Pass No Flaming Drips
Smoke Generation (Flaming)
ASTM E662 (NFPA 258)
Ds 41@1.5 Min Ds 94@4.0 Min
Smoke Generation (Non-Flaming)
ASTM E662 (NFPA258)
Ds 7@1.5 Min Ds 45@4.0 Min
Toxic Gas Generation
BOMBARDIER SMP 800-C
Pass
Toxicity Index
NES 713
3.9
* Test data is based on controlled laboratory conditions and does not necessariy reflect performance in actual fire conditions. Additional product nformation avialble upon request.
TYPE - ZHLA Non - Halogen, Low Smoke and Low Flame Spread make Type ZHLA a proven choice for applications where limiting toxic materials of combustion are an important issue. Since ZHLA is also UL listed, it is ideal for field installation in confined, public areas such as subways, tunnels, etc.
CONSTRUCTION: ZHLA has a flexible inner core made from a spiral wound strip of heavy gauge, hot-dipped galvanized steel. The 3/8 through 1-1/4 inch trade sizes contain an integral bonding strip of copper. The 1-1/2 inch and larger are designed with a fully interlocked strip. The specially formulated thermoplastic black polyurethane jacket has excellent flame resistance and low smoke & toxicity generation characteristics. It is also resistant to Ozone, Hydrocarbons, Moderate Chemicals, Oils and Fuels.
APPLICATION: There are many situations and areas where PVC is not allowed for electrical construction. The jacketing material used for ZHLA virtually eliminates the release of acidic gases found in PVC products.
-Meets the requirements of Bombardier SMP 800-C for Toxic Gas Generation. -Meets the requirements of both ASTM E162 for Flame Spread and ASTM E662 for Smoke Generation.
This conduit is intended for installation in accordance Article 350 of the NEC (ANSI/NFPA-70): -Permitted for use in exposed or concealed locations. -Installations under raised floors in Data Processing Areas. Article 645-5(d)(2) -Listed and marked for direct burial and in poured concrete. -For containment of 600 volts and lower potential circuits.
-Sunlight resistant.
-Suitable as a grounding conductor when used for circuits rated up to 20A for the 3/8 & 1/2 inch trade sizes and 60A for the 3/4 through 1-1/4 inch trade sizes in lengths six feet or less per Article 250.118(7).
-Installations in hazardous (classified) locations:
Class I Div. 2 Article 501.4(B)
Class II Div. 1 & 2 Article 502.4
Class III Div. 1 & 2 Article 503.3
-Installed under raised floors in Data Processing Areas Aticles 645.5 (D)(2) -Elevators and Hoistways Article 620.21
Listed File # E29278. Conforms to Underwriters Laboratories Standard ANSI/UL-360 for Liquidtight Flexible Steel Conduit.