Part of the Stainless Steel Flexible Conduit Family.
A UL-listed liquidtight stainless steel flexible conduit that is designed specifically for hot or cold environments and provides excellent corrosion-resistance. The specially formulated PVC jacket remains flexible at low temperatures and resists aging at elevated temperatures.
CONSTRUCTION:
Inner Core:
- Corrosion-resistant continuous strip of 316L Stainless Steel
- 1/2″ – 2″ Fully Interlocked Profile
Liquidtight Jacket:
- Flexible PVC
- Resistant to Oils and Mild Acids
- Flame Retardant
- Sunlight Resistant (UV)
- High / Low Temperature Range
APPLICATION:
- Formerly Type ATSS
- Non-UL 3″ through 4″ available upon request
- Machine Tools, Ovens, Foundries, Refrigeration
- Industrial Environments with High / Low Temperatures
- Corrosive Atmospheres
- Wet and Oily Locations
- Outdoor use due to the inherent UV resistance of PVC
- Extreme Climatic Conditions
- Compatible with standard liquidtight connectors
- Designed to be used with high temperature machine tool wiring.
This conduit is intended for installation in accordance with Article 350 of the NEC (ANSI/NFPA-70) and in section 14.5.4 of the ANSI/NFPA-79 Standard for Industrial Machinery:
- Listed and marked for Direct Burial and in Poured Concrete
- Permitted for use in exposed or concealed locations.
- Installations under raised floors in Data Processing Areas Article 645.5(E)
- Listed and marked for direct burial and in poured concrete.
- For containment of 1000 volts and lower-potential circuits.
- Permitted for service entrance wiring to 6 feet. Article 230.43
- Sunlight-resistant
- Use Separate Grounding Conductor — If liquidtight flexible metal conduit contains a stainless-steel core, a wire-type equipment grounding conductor or a bonding jumper in accordance with 250.102(E) (2) shall be installed. Article 250.118 (A)(6)(f).
- Installations in hazardous (classified) locations:
- Class I Div. 2: Article 501.10 (B)(2) & 501.30(B)
- Class II Div. 1: Article 502.10(A)(2) & 502.30(B) Div. 2: 502.10(B)(2)
- Class III Div. 1: Article 503.10(A)(3) & 503.30(B) Div. 2: 503.10(B)
- Use as Feeders and Services at Marinas and Boatyards. Article 553.7(B).
- Wiring on Building. Article 225.10.
- Conductor Enclosers Adjacent to Motors over 1000V. Article 430.223.
- Underground Service, Feeder, Branch Circuit, and Recreational Vehicle Site Feeder Circuit Conductors. Article 551.80.
- Elevators and Hoistways. Article 620.21.
- Pools and Fountains. Article 680.
- Bodies of water. Article 682.
- Fire pumps. Article 695
- Meets the same specifications as Type LA.
Markets:
Defense, Mining, Oil & Gas Refineries, Power Plants, Ship Building, Steel Mills, Utilities, Wastewater Treatment
All Products Proudly Made in the USA